Room sensors


Filter
CAB-02

Accessoires

USB cable for OPP-Room for configuring OPP-Room transmitters.
For configuring outputs, controller settings,
display brightness, alarm thresholds (LCD display
color change ), bus settings, etc. Galvanic
isolation included. For use with the OR-C
OPP-Room configuration software (see the download
area of our website).
Data sheet no. 20560
CO2-W-D-2.5

Air quality

CO2 and temp. transducer without LCD display
For indoor installation. Measuring range CO2: 0 –
3,000 ppm, (factory calibrated to 0 – 2,000 ppm).
Measuring range, temperature: 0 – 50 °C. For
demand-based control of ventilation systems. The
measuring principle is based on non-dispersive
infrared technology with automatic
self-calibration. 5 year service intervals. 2
linear analog outputs OUT1 (CO2) and OUT2
(temperature) adjustable between 0 – 10 V DC and
4 – 20 mA using jumpers. Additional jumper for
offsetting the 0-point to +20%. Power supply: 24
V AC/DC ± 20% Housing for interior vertical wall
mounting. Housing: 97 x 61 x 19 mm (H x W x D),
white. Protection class: IP 30.
Data sheet no. 14101
CO2-WD-LC

Air quality

CO2–W air quality sensor CO2 with display
For indoor installation. Measuring range: 0 –
3,000 ppm CO2, (factory calibrated to 0 – 2,000
ppm). For demand-based control of ventilation
systems depending on the number of people. Air
flows through the air sampling tube, over the
sensor and back into the air duct. The measuring
principle is based on non-dispersive infrared
technology with automatic self-calibration. 5
year service intervals. 2 linear analog outputs
(CO2): OUT1: fixed 0 – 10 V DC and OUT2: 2 – 10 V
DC or 4 – 20 mA configurable using jumpers. Power
supply: 24 V AC/DC ± 20% Housing for interior
vertical wall mounting. Housing: 100 x 80 x 28 mm
(H x W x D), white. Protection class: IP 30.
Data sheet no. 14106
CO2-WD-LC-FAI

Air quality

CO2-W air quality sensor CO2 with display and LED lights
For indoor installation. Measuring range: 0 –
3,000 ppm CO2, (factory calibrated to 0 – 2,000
ppm). For demand-based control of ventilation
systems depending on the number of people. Air
flows through the air sampling tube, over the
sensor and back into the air duct. The measuring
principle is based on non-dispersive infrared
technology with automatic self-calibration.
Service interval longer than 5 years. Output: 0 –
10 V at 0 – 2,000 ppm. Alarm: acoustic (94 dB,
mute button) and with red, yellow and green LED.
Optical via LEDs, factory-configured to green: 0
– 800 ppm, yellow: 800 – 1400 ppm, red: > 1,400
ppm. Power supply: 24 V AC/DC ± 20% Housing for
interior vertical wall mounting. Housing: 100 x
80 x 28 mm (H x W x D), white. Protection class:
IP 30.
Data sheet no. 14106
CO2TRH-W-D m. Touchfarbdisplay

Air quality

CO2, temperature and humidity transducers. 3 x 0 – 10 V, relay, Mod/BAC output.
3–way transmitter. For indoor installation. Large,
illuminated color touchscreen (36x49 mm).
Configurable via the display. Sensor metrics and
measuring ranges: CO2: 0 – 2,000 ppm (0 – 10 V,
Mod, BAC) Temperature: 0 – 50 °C (0 – 10 V, Mod,
BAC) Relative humidity: 0–100% (0 – 10 V, Mod,
BAC) Display configurable as alternating or
fixed. Graph for all 3 sensor metrics. 2 limit
indications can be programmed per sensor metric.
Color changes to yellow or red if the limit is
exceeded. Modbus + BACnet interface as a standard
feature. Relay output for CO2 (switching relay,
loadable from 1 mA/5 V to 1 A/50 V AC/24 V DC),
activated at 1,000 ppm CO2, hysteresis 100 ppm
(configurable). For demand-based control of
ventilation systems. The CO2 measuring principle
is based on non-dispersive infrared technology
with automatic self-calibration. 5 year service
intervals. Power supply: 24V AC/DC ± -20% Power
consumption < 0.6 W m. Display, max. 2 W peak.
Permissible ambient conditions 0 – 50°C, 0 –
95%rH. Non-condensing. Perm. storage temp. -30 –
+70°C. Housing for vertical wall mounting, white.
Protection class: IP 20. Screw terminals max. 1.5
mm². Dimensions: approx. 83x122x23 mm (W x H x
D).
Data sheet no. 14110
OPP-HSC 1.01

Safety

Room hygrostat potentiometer with outdoor setting
For the monitoring and control of the relative
humidity in rooms. Measuring range: 30 – 90% rH
Contact load: max. 5 A, 230 V AC min. 100 mA at
24 V Dimensions: 76 x 76 x 34 mm (L x W x H with
base)
Data sheet no. 20632
OPP-HSC 1.10

Safety

Room hygrostat potentiometer with indoor setting
For the monitoring and control of the relative
humidity in rooms. Measuring range: 30 – 90% rH
Contact load: max. 5 A, 230 V AC min. 100 mA at
24 V Dimensions: 76 x 76 x 34 mm (L x W x H with
base)
Data sheet no. 20632
OPP-PIR-1

Presence and brightness

presence detector with temperature 24 V AC/DC
In white housing with base. Detection angle 110
°C, detection distance at 2.4 m Height: 15 m
adjustable delay relay 0.1 – 10 minutes and
overrun relay 0.1 – 30 min. potential-free
changeover contact. The presence detector works
with intelligent pulse counting to largely
prevent false alarms. The pulse counting can be
set to 1 or 2 pulse detection. The output signal
is only present if the number of set pulses is
detected within a specified time period. Contact
output loadable with 24 V/3 A. Housing
dimensions: 67 x 115 x 48 mm (W x H x D), with
additional min./max temperature limits.
Protection class: IP 20 incl. console MB 99 for
wall and ceiling mounting
Data sheet no. 15603
OPP-PIR-2

Presence and brightness

Presence detector for ceiling mounting 24 V AC/DC
In white housing with base. Detection range 360°
adjustable delay and overrun relay 0.1 – 25
minutes, potential-free changeover contact. The
presence detector is a passive infrared sensor
with detection thresholds for movement and
presence and was specifically developed for
ventilation and air conditioning systems. The
max. mounting height is 4.2 m. Dimensions: 110 mm
Ø x 40 mm height. Protection class: IP 41
Data sheet no. 15601